Air for combustion, ventilation, and dilution of flue gases must be provided for appliances installed in buildings by one of the methods described in Sections 304.5 through 304.9 of the 2023 Florida Fuel Gas Code.
The minimum required indoor volume is calculated as:
Required Volume (ft³) = (Total Appliance Input in Btu/h ÷ 1,000) × 50
For appliances other than fan-assisted:
Required Volume = (Other Appliance Input ÷ 1,000) × (21 ÷ ACH)
For fan-assisted appliances:
Required Volume = (Fan Appliance Input ÷ 1,000) × (15 ÷ ACH)
Sections 304.6 through 304.12 cover alternative provisions including:
All installations must comply with manufacturer instructions and the Florida Fuel Gas Code.
Reference: 2023 Florida Fuel Gas Code (IFGS) – Section 304